Swimming pool at recreation park De Kuilart
A healthier swimming environment with lower water and energy costs
Installing a UV system significantly reduced water and energy costs. Additionally, it created a more enjoyable swimming environment and improved comfort for staff due to demonstrably better water and air quality.

UV Solution:
A UV system with three low-pressure lamps treats 200 m³ per hour.
UV Results:
Combined chlorine levels dropped from approximately 0.6 mg/l to between 0.2 and 0.4 mg/l.
UValue Creation:
- Water savings: 643 m³ per month
- Energy savings: 10,645 kWh per month
Reduce operational costs
By reducing the backwash frequency from seven times to once per week, 150 m³ of water is saved weekly. With average costs, this results in €643 saved per month. Additionally, lower heat losses and reduced reheating of supplementary water contribute to an energy savings of €3,140 per month.
The Challenge: high combined chlorine levels
Swimming pool De Kuilart is a swimming paradise located on the Frisian Lakes. The newly built pool (2022) features three slides, a large toddler area, and a competition pool, making it a popular destination for tourists and locals alike. During summer, it attracts up to 1,200 visitors per day. However, with so many people in the pool, high levels of combined chlorine became an issue.
We knew that with the new Environmental Act, combined chlorine levels must not exceed 0.6 mg/l. While our state-of-the-art water treatment system had improved things, it was challenging to stay below that threshold on busy days. Our staff often complained about irritated eyes.
Owner Wouter Bleckman

Situation before the UV installation
Maintaining the pool required large amounts of water and chemicals: 25 m³ per backwash, performed daily during the peak season. This water had to be heated from tap water temperature to swimming pool temperature and treated with sulfuric acid and chlorine to ensure safety. These chemicals contributed to unpleasant air quality.

Results after installation of the UV system
After installing the UV system, backwashing is needed only once per week, significantly reducing water and energy costs, especially during the peak season.
Energy savings through smart UV usage
Additionally, a nighttime program between 10 PM and 8 AM lowers the circulation pump speed and turns off the UV system. This reduces energy use and lamp wear by approximately 30%. The system runs 24/7 only during the eight weeks of the peak season.
“Since installing the UV system, air quality has improved so much that our staff no longer experience any complaints while working in the pool. That’s very important to me. The purchase has been a success on every level. I’m truly happy with it.”

Case study facts:
Organization name: Swimming pool at recreation park De Kuilart
Location: Koudum, the Netherlands
UV system supplier: Van Remmen UV Technology